Recognition and Location of Power Transformer Turn to Turn Fault by Analysis of Winding Imposed Forces
(ندگان)پدیدآور
Torkaman, A.Naeini, V.نوع مدرک
TextResearch paper
زبان مدرک
Englishچکیده
Turn to turn fault is one of the major internal failures in the power transformers that if it is not quickly detected, can be extended and led to a complete transformer breakdown. So, the diagnosis and location of the turn to turn fault of the power transformer, as one of the most important equipment in the power system, is the main objective of this paper. For this purpose, a detailed model of a three-phase transformer is presented by the finite element method (FEM) to investigate this fault in the different situations. Accordingly, the number of short-circuit turns as well as fault location, cause to generate the high forces between the short-circuit turns and the other healthy winding turns. Consequently, in this paper an appropriate method based on force analysis of winding turns for detecting, locating and determining fault severity is introduced.
کلید واژگان
turn to turn faultRecognition
location
imposed forces
FEM
شماره نشریه
2تاریخ نشر
2019-10-011398-07-09
ناشر
University of Mohaghegh Ardabiliدانشگاه محقق اردبیلی
سازمان پدید آورنده
Department of Electrical Engineering, Malayer University, Malayer, Iran.Department of Electrical Engineering, Malayer University, Malayer, Iran.
شاپا
2322-45762423-4567