نمایش مختصر رکورد

dc.contributor.authorTorkaman, A.en_US
dc.contributor.authorNaeini, V.en_US
dc.date.accessioned1399-07-09T03:04:20Zfa_IR
dc.date.accessioned2020-09-30T03:04:20Z
dc.date.available1399-07-09T03:04:20Zfa_IR
dc.date.available2020-09-30T03:04:20Z
dc.date.issued2019-10-01en_US
dc.date.issued1398-07-09fa_IR
dc.date.submitted2019-01-16en_US
dc.date.submitted1397-10-26fa_IR
dc.identifier.citationTorkaman, A., Naeini, V.. (2019). Recognition and Location of Power Transformer Turn to Turn Fault by Analysis of Winding Imposed Forces. Journal of Operation and Automation in Power Engineering, 7(2), 227-234. doi: 10.22098/joape.2019.5735.1428en_US
dc.identifier.issn2322-4576
dc.identifier.issn2423-4567
dc.identifier.urihttps://dx.doi.org/10.22098/joape.2019.5735.1428
dc.identifier.urihttp://joape.uma.ac.ir/article_783.html
dc.identifier.urihttps://iranjournals.nlai.ir/handle/123456789/233017
dc.description.abstractTurn to turn fault is one of the major internal failures in the power transformers that if it is not quickly detected, can be extended and led to a complete transformer breakdown. So, the diagnosis and location of the turn to turn fault of the power transformer, as one of the most important equipment in the power system, is the main objective of this paper. For this purpose, a detailed model of a three-phase transformer is presented by the finite element method (FEM) to investigate this fault in the different situations. Accordingly, the number of short-circuit turns as well as fault location, cause to generate the high forces between the short-circuit turns and the other healthy winding turns. Consequently, in this paper an appropriate method based on force analysis of winding turns for detecting, locating and determining fault severity is introduced.en_US
dc.format.extent1129
dc.format.mimetypeapplication/pdf
dc.languageEnglish
dc.language.isoen_US
dc.publisherUniversity of Mohaghegh Ardabilien_US
dc.publisherدانشگاه محقق اردبیلیfa_IR
dc.relation.ispartofJournal of Operation and Automation in Power Engineeringen_US
dc.relation.ispartofمجله بهره برداری و اتوماسیون در مهندسی قدرتfa_IR
dc.relation.isversionofhttps://dx.doi.org/10.22098/joape.2019.5735.1428
dc.subjectturn to turn faulten_US
dc.subjectRecognitionen_US
dc.subjectlocationen_US
dc.subjectimposed forcesen_US
dc.subjectFEMen_US
dc.titleRecognition and Location of Power Transformer Turn to Turn Fault by Analysis of Winding Imposed Forcesen_US
dc.typeTexten_US
dc.typeResearch paperen_US
dc.contributor.departmentDepartment of Electrical Engineering, Malayer University, Malayer, Iran.en_US
dc.contributor.departmentDepartment of Electrical Engineering, Malayer University, Malayer, Iran.en_US
dc.citation.volume7
dc.citation.issue2
dc.citation.spage227
dc.citation.epage234
nlai.contributor.orcid0000-0002-2446-1229


فایل‌های این مورد

Thumbnail

این مورد در مجموعه‌های زیر وجود دارد:

نمایش مختصر رکورد