    Exergy Analysis of an Air Dehumidification System Equipped with Mixing Box and Heat Exchanger Heat Recovery Units

    (ندگان)پدیدآور
    Jafarinejad, TohidYousefi, HosseinFathi, AmirhosseinChoubineh, Kianoosh
    Thumbnail
    دریافت مدرک مشاهده
    FullText
    اندازه فایل: 
    667.7کیلوبایت
    نوع فايل (MIME): 
    PDF
    نوع مدرک
    Text
    Research Article
    زبان مدرک
    English
    نمایش کامل رکورد
    چکیده
    Exergy analysis emboldens in cases that all the inefficiencies and bottlenecks to improve energy systems are to be addressed. In this study, a novel vapor compression air dehumidifier integrated with an auxiliary heat exchanger in series arrangement with the main condenser in order to mitigate the reheat coil, and an extra mixing box to recover the ventilated air heat has been introduced. A comprehensive methodology for exergetic analysis of vapor compression heating ventilation and air conditioning systems has been presented. The quasi-dynamic component-by-component exergy analyses of both the conventional and novel air dehumidification systems have been conducted for a specific outside air fraction. Also, sensitivity analyses have been conducted on the exergy destruction and efficiency as a function of outside air fraction. Results denote that for the outside air fraction of 53%, exergy destruction of the novel air dehumidification system has decreases up to 32.4% and exergy efficiency has ramped up by 53.45%. Moreover, by rising the outside air fraction from none to 100%, exergy destruction in the novel air dehumidification system has declined by 46% to 30.5 %, and exergy efficiency has undergone a 106% to 40.3 % increase compared with the conventional system depending on the outside.
    کلید واژگان
    Exergy analysis
    exergy destruction
    Exergy efficiency
    HVAC systems
    Heat Recovery

    شماره نشریه
    3
    تاریخ نشر
    2019-08-01
    1398-05-10
    ناشر
    Iranian Association for Energy Economics
    سازمان پدید آورنده
    Department of Energy Engineering, Sharif University of Technology, Tehran, Iran
    Department of Renewable Energy and Environment Faculty of New Sciences and Technologies, university of Tehran, Tehran, Iran
    School of Mechanical Engineering, Shiraz University, Shiraz, Iran
    Department of Renewable Energies and Environment, Faculty of New Sciences and Technologies, University of Tehran, Tehran, Iran

    شاپا
    2538-4988
    2676-4997
    URI
    https://dx.doi.org/10.22097/eeer.2019.170335.1068
    http://www.eeer.ir/article_88625.html
    https://iranjournals.nlai.ir/handle/123456789/95316

    مرور

    همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

    حساب من

    ورود به سامانهثبت نام

    آمار

    مشاهده آمار استفاده

    تازه ترین ها

    تازه ترین مدارک
    © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
    تماس با ما | ارسال بازخورد
    قدرت یافته توسطسیناوب