      Design and operation optimization of an air conditioning system through simulation: an hour-by-hour simulation study

      (ندگان)پدیدآور
      Ahmadzadehtalatapeh, MohammadHuangYau, Yat
      Thumbnail
      دریافت مدرک مشاهده
      FullText
      اندازه فایل: 
      1.020 مگابایت
      نوع فايل (MIME): 
      PDF
      نوع مدرک
      Text
      Research Paper
      زبان مدرک
      English
      نمایش کامل رکورد
      چکیده
      In the present research, performance validation of a Heating, Ventilation, and Air Conditioning (HVAC) system operating in a library building was conducted. The operating HVAC system was studied in terms of the provided indoor air conditions and energy consumption level. The fieldwork measurements showed that the HVAC system is not capable of providing the desired indoor air conditions based on the ASHRAE standards. Therefore, two deciding design and operating parameters namely, chilled water cooling coil number of rows and chilled water temperate were investigated to achieve possible improvement in the system performance. For this purpose, different numbers of rows for cooling coil design at different chilled water temperatures were examined. TRNSYS software was employed to investigate the hourly effect of the variables on the system for a whole year of operation.Based on the simulation results, the provided indoor air conditions were appropriate and within the comfort area with the two-row configuration cooling coil. However, the energy performance of the system indicated that the two-row configuration with 10 chilled water temperature was superior in terms of energy consumption, and could provide the desired indoor air conditions, thus it was recommended to be implemented in the existing system.
      کلید واژگان
      energy consumption
      HVAC System
      Indoor Air Conditions
      TRNSYS

      شماره نشریه
      2
      تاریخ نشر
      2018-06-01
      1397-03-11
      ناشر
      University of Tehran
      سازمان پدید آورنده
      Department of Marine and Mechanical Engineering, Chabahar Maritime University, 99717-56499, Chabahar, Iran
      Department of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia

      شاپا
      2383-1111
      2345-251X
      URI
      https://dx.doi.org/10.22059/ees.2018.31534
      http://www.energyequipsys.com/article_31534.html
      https://iranjournals.nlai.ir/handle/123456789/95162

      مرور

      همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

      حساب من

      ورود به سامانهثبت نام

      تازه ترین ها

      تازه ترین مدارک
      © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
      تماس با ما | ارسال بازخورد
      قدرت یافته توسطسیناوب