Analysis of effective factors on transient ground potential rise in gas insulated substations
(ندگان)پدیدآور
Moravej, ZahraBabaei, MaziarBagheri, Sajadنوع مدرک
TextResearch Paper
زبان مدرک
Englishچکیده
This study presents the manner in which transient modeling concepts, which are fully analyzed in the referred standards, are implemented, for the purpose of evaluating the Transient Ground Potential Rise (TGPR). This is a phenomenon of 10–100kV voltages with up to 10µs duration on the grounded enclosure of Gas Insulated Substations (GIS), which may cause concern for personnel safety and problems for protection and control circuits in substations. This article summarizes the results of the investigation for influential factors on TGPR, such as, different contingency conditions and grounding system models. This article focuses on the TGPR study of "Siah-bishe" 400kV gas insulated substation. The study was carried out by modeling all pieces of equipment in the ElectroMagnetic Transients Program (EMTP)-RV, with careful consideration of different modeling guidelines and instructions described in the available standards.
کلید واژگان
EMTP-RVGas Insulated Substations
Transient Enclosure Voltage
Transient Ground Potential Rise (TGPR)
Very Fast Transient (VFT)
شماره نشریه
2تاریخ نشر
2015-12-011394-09-10
ناشر
University of Tehranسازمان پدید آورنده
Faculty of Electrical & Computer Engineering, Semnan University, Semnan, IranFaculty of Electrical & Computer Engineering, Semnan University, Semnan, Iran
Faculty of Electrical & Computer Engineering, Semnan University, Semnan, Iran
شاپا
2383-11112345-251X