      STATOR TURN-TO-TURN FAULT DETECTION OF SYNCHRONOUS GENERATOR USING TOTAL HARMONIC DISTORTION (THD) ANALYZING OF MAGNETIC FLUX LINKAGE

      (ندگان)پدیدآور
      پدیدآور نامشخص
      Thumbnail
      دریافت مدرک مشاهده
      FullText
      اندازه فایل: 
      918.8کیلوبایت
      نوع فايل (MIME): 
      PDF
      نوع مدرک
      Text
      زبان مدرک
      English
      نمایش کامل رکورد
      چکیده
      Diagnostics of synchronous generator turn-to-turn faults can be accomplished byanalyzing the anomalies of machine local variable such as magnetic flux linkage. On the otherhand, because current transformers and voltage transformers are usually installed in the machinefor different purposes as default, the monitoring schemes that depend on the study of these inputshave become a topic of interest. As a consequence, in the last two decades, a variety of methodshave been proposed based only on the global external variable (such as stator current and voltage).It must be noted that the global external variable analysis techniques are not capable of detectingall of the potential faults in electrical machines and some researches, including this work, aim totransfer a part of the global external variables analysis knowledge to techniques that monitor thesignatures produced by the fault to the electromagnetic flux signals (local variable). Hence, thiscontribution deals with the analysis of the stator turn-to-turn short circuit fault of salient-polesynchronous generator. In this paper, a fault indicator based on harmonic analysis of the magneticflux linkage is investigated. Experimental results derived from a 4-pole, 380V, 1500 rpm, 50 Hz,50 KVA, 3-phase salient-pole synchronous generator, show that the proposed method is useful andeffective.
      کلید واژگان
      Synchronous generator
      inter-turn fault
      magnetic flux linkage
      harmonic analysis

      شماره نشریه
      2
      تاریخ نشر
      2013-12-01
      1392-09-10
      ناشر
      Shiraz University

      شاپا
      2228-6179
      URI
      https://dx.doi.org/10.22099/ijste.2013.1886
      http://ijste.shirazu.ac.ir/article_1886.html
      https://iranjournals.nlai.ir/handle/123456789/45255

      مرور

      همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

      حساب من

      ورود به سامانهثبت نام

      تازه ترین ها

      تازه ترین مدارک
      © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
      تماس با ما | ارسال بازخورد
      قدرت یافته توسطسیناوب