      Evaluating the Improvement of Partial Discharge Localization Accuracy Using Frequency Response Assurance Criterion

      (ندگان)پدیدآور
      Mohammadirad, AmirVakili, RaminShayegani Akmal, A.A.
      Thumbnail
      دریافت مدرک مشاهده
      FullText
      اندازه فایل: 
      379.6کیلوبایت
      نوع فايل (MIME): 
      PDF
      نوع مدرک
      Text
      Research Paper
      زبان مدرک
      English
      نمایش کامل رکورد
      چکیده
      Partial Discharge (PD) is the most important source of insulation degradation in power transformers. In order to prevent catastrophic failures in transformers, PDs need to be located as soon as possible so that maintenance measures can be taken in time. Due to the structural complexity of windings, locating the PD source inside a transformer winding is not a simple task. In this paper, the efficacy of the proposed Frequency Response Assurance Criterion (FRAC) correlation technique for finding the location of a PD source in a transformer winding is evaluated and compared with two well-known correlation techniques in this regard, that are Time domain correlation and Kullback- Leibler divergence. The responses of the winding to PD pulses, generated by Heidler function, of known pulse duration applied in parallel along the whole sections of the winding are considered as the reference data. In addition, the captured responses of the winding generated by injecting the PD pulses of arbitrary shapes and magnitude along the various sections of the winding are taken as the test data. Subsequently, the location of the PD source is determined by finding the maximum FRAC value between the reference signals and the test signal. First, a simulation case-study is carried out to show how the proposed method can be applied to locate a PD source. Subsequently, the results of the proposed method are compared with the time-domain and Kullback–Leibler divergence correlation techniques. Finally, the proposed method is validated with the experimental results. The simulation and experimental results demonstrate that the proposed method is more effective in precisely determining the location of a PD source even in a very noisy condition.
      کلید واژگان
      Partial discharge
      Correlation method
      Transformer winding
      FRAC
      PD location

      شماره نشریه
      03
      تاریخ نشر
      2018-09-01
      1397-06-10
      ناشر
      Islamic Azad University,Central Tehran Branch
      سازمان پدید آورنده
      School of Electrical and Computer Engineering, University of Tehran ,Tehran, Iran
      School of Electrical and Computer Engineering, University of Tehran ,Tehran, Iran
      School of Electrical and Computer Engineering, University of Tehran ,Tehran, Iran

      شاپا
      2251-9246
      2345-6221
      URI
      http://ijsee.iauctb.ac.ir/article_664106.html
      https://iranjournals.nlai.ir/handle/123456789/308568

      مرور

      همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

      حساب من

      ورود به سامانهثبت نام

      تازه ترین ها

      تازه ترین مدارک
      © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
      تماس با ما | ارسال بازخورد
      قدرت یافته توسطسیناوب