Analysis of Gasketed-plate Heat Exchanger Performance Using Nanofluid
(ندگان)پدیدآور
Bozorgan, NavidShafahi, Maryamنوع مدرک
TextFull Lenght Research Article
زبان مدرک
Englishچکیده
A heat exchanger using nanofluid needs to operate at optimum mass concentration level to get the maximum heat transfer performance. A numerical analysis is performed on the heat transfer and pressure drop of water-based γ-Al2O3 nanofluid gasketed-plate heat exchanger to specify its optimum conditions. Cold water will be heated by γ-Al2O3/water nanofluid. The results showed that optimal volume concentration of γ-Al2O3/water nanofluid based on a maximum performance index is about 0.016. The heat transfer rate at the optimal concentration of nanofluid is approximately 12.3% higher than that of pure water (base fluid), while pumping power is increased by 1.15%. With regard to 1% enhancement in heat transfer rate with increasing ϕ values from ϕ=0.016 to ϕ=0.028 (optimum volume concentration for maximum heat transfer rate) and the pumping power required for nanofluid, the optimum concentration for maximum performance index is selected as the best level of particle volume fraction for γ-Al2O3/water nanofluid in this research.
کلید واژگان
NanofluidParticle volume fraction
Gasketed-plate heat exchanger
Heat transfer
Pressure drop
Nano Heat transfer
شماره نشریه
1تاریخ نشر
2017-04-011396-01-12
ناشر
Semnan University Pressسازمان پدید آورنده
Islamic Azad University of AbadanCalifornia State Polytechnic University, Pomona, California, USA
شاپا