    Impact of Pollution Location on Time and Frequency Characteristics of Leakage Current of Porcelain Insulator String under Different Humidity and Contamination Severity

    (ندگان)پدیدآور
    Mirzaie, M.Azizi Tousi, A.
    Thumbnail
    دریافت مدرک مشاهده
    FullText
    اندازه فایل: 
    481.7کیلوبایت
    نوع فايل (MIME): 
    PDF
    نوع مدرک
    Text
    Research paper
    زبان مدرک
    English
    نمایش کامل رکورد
    چکیده
    One of the important factors influencing outdoor insulators performance is pollution phenomenon. The pollution, especially during humidity condition, reduces superficial resistance of insulator and lead to a flow of Leakage Currents (LC) on the insulator surface, which may result in total flashover. The LC characteristics are affected by parameters such as nature and severity of pollution. Location of pollution is another parameter that can be effective. This paper presents the analysis of LC waveforms of insulator strings under different pollution location and Equivalent Salt Deposit Density (ESDD). The tests was performed on the HV porcelain suspension insulator string in which three adjacent discs of insulator string were contaminated and location of them changes along the insulator string. Besides, the effect of humidity and operating voltage on LC waveforms were investigated. Experimental data were analyzed in both time and frequency domain. Obtained results indicate that there is strong correlation between the location of pollution and LC parameters such as peak value ( ), harmonic components and Total Harmonic Distortion (THD). Also, the ratio of fifth to third harmonic component ( ) is presented as an important index that has strong relationship to the pollution location.
    کلید واژگان
    Humidity
    Insulator
    leakage current
    Pollution

    شماره نشریه
    2
    تاریخ نشر
    2013-11-01
    1392-08-10
    ناشر
    University of Mohaghegh Ardabili
    دانشگاه محقق اردبیلی
    سازمان پدید آورنده
    Faculty of Electrical and Computer Engineering, Babol University of Technology, Babol, Iran.
    Faculty of Electrical and Computer Engineering, Babol University of Technology, Babol, Iran.

    شاپا
    2322-4576
    2423-4567
    URI
    http://joape.uma.ac.ir/article_178.html
    https://iranjournals.nlai.ir/handle/123456789/232968

    مرور

    همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

    حساب من

    ورود به سامانهثبت نام

    آمار

    مشاهده آمار استفاده

    تازه ترین ها

    تازه ترین مدارک
    © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
    تماس با ما | ارسال بازخورد
    قدرت یافته توسطسیناوب