    Characterization of Power Transformer Electromagnetic Forces Affected by Winding Faults

    (ندگان)پدیدآور
    Behjat, V.Shams, A.Tamjidi, V.
    Thumbnail
    دریافت مدرک مشاهده
    FullText
    اندازه فایل: 
    972.7کیلوبایت
    نوع فايل (MIME): 
    PDF
    نوع مدرک
    Text
    Research paper
    زبان مدرک
    English
    نمایش کامل رکورد
    چکیده
    Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush currents, can cause the windings to be deform, rupture, and/or displace, if the transformer and winding holders structure is not designed or assembled properly. Also, these mechanical changes can damage insulation between two or more adjacent turns of a winding and so, produce the local inter-turn fault. Occurrence of any fault in windings will change the electromagnetic force distribution in transformers and will cause developing secondary faults. Hence, this contribution is aimed at characterizing the electromagnetic forces behavior in power transformers and determines the changes of force values after occurring winding mechanical and inter-turn. The study keeps at disposal a two-winding, three phase, 8 MVA power transformer, on their windings faults are imposed and investigated through the FEM analysis. The accuracy of the created FEM model is firstly validated using analytical methods for transformer healthy condition, and then the winding shorted turn fault along with the mechanical faults are considered using 3D FEM model. The extracted characteristic signatures attained to different type of winding faults is expected to be useful at the design stage of power transformers.
    کلید واژگان
    Power transformer
    Electromagnetic forces
    Finite element method (FEM)
    Interturn fault
    Winding mechanical fault
    Transformers

    شماره نشریه
    1
    تاریخ نشر
    2018-06-01
    1397-03-11
    ناشر
    University of Mohaghegh Ardabili
    دانشگاه محقق اردبیلی
    سازمان پدید آورنده
    Department of Electrical Engineering, Azarbaijan Shahid Madani university, Tabriz, Iran. Email: behjat@azaruniv.edu
    Department of Electrical Engineering, Engineering Faculty, Azarbaijan Shahid Madani University, Tabriz, Iran
    Department of Electrical Engineering, Engineering Faculty, Shahid Madani University, Tabriz, Iran

    شاپا
    2322-4576
    2423-4567
    URI
    https://dx.doi.org/10.22098/joape.2018.2436.1210
    http://joape.uma.ac.ir/article_635.html
    https://iranjournals.nlai.ir/handle/123456789/232947

    مرور

    همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

    حساب من

    ورود به سامانهثبت نام

    آمار

    مشاهده آمار استفاده

    تازه ترین ها

    تازه ترین مدارک
    © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
    تماس با ما | ارسال بازخورد
    قدرت یافته توسطسیناوب