A new algorithm for three-phase power transformer differential protection considering effect of ultra-saturation phenomenon
(ندگان)پدیدآور
Noshad, BahramRazaz, MortezaSeifossadat, Seyed Ghodratollahنوع مدرک
Textزبان مدرک
Englishچکیده
One of transient phenomenon that leads to the false trip of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, at first a new algorithm for three-phase power transformer differential protection considering effect of the ultra-saturation phenomenon is presented.To model the ultra-saturation phenomenon, the nonlinear characteristic of the transformer core and the effect of the saturation of the current transformers are taken into account. It is assumed that the load of the transformer is a resistive and inductive load. In this algorithm, the ultra-saturation phenomenon, external and internal faults of power transformer and magnetic inrush current are simulated and appropriate criteria using signal harmonic components of differential currentwill be presentedfor distinguish between these phenomenon by DiscreteFourier Transform (DFT) algorithm. In this paper, simulation is done by PSCAD and MATLAB programs
کلید واژگان
three-phase power transformer differential protectionultra-saturation phenomenon
magnetic inrush current
internal faults
external faults
false trip
harmonic components
and differential current
شماره نشریه
3تاریخ نشر
2014-06-011393-03-11
ناشر
Sharif University of Technologyسازمان پدید آورنده
Department of Electrical Engineering, Shahid Chamran University of Ahvaz, Ahvaz, IranDepartment of Electrical Engineering, Shahid Chamran University of Ahvaz, Ahvaz, Iran
Department of Electrical Engineering, Shahid Chamran University of Ahvaz, Ahvaz, Iran
شاپا
1026-30982345-3605