نمایش مختصر رکورد

dc.contributor.authorSamet, Haidaren_US
dc.contributor.authorJarrahi, Mohammad Aminen_US
dc.date.accessioned1399-07-09T06:45:14Zfa_IR
dc.date.accessioned2020-09-30T06:45:14Z
dc.date.available1399-07-09T06:45:14Zfa_IR
dc.date.available2020-09-30T06:45:14Z
dc.date.issued2014-11-01en_US
dc.date.issued1393-08-10fa_IR
dc.date.submitted2016-01-06en_US
dc.date.submitted1394-10-16fa_IR
dc.identifier.citationSamet, Haidar, Jarrahi, Mohammad Amin. (2014). A Comparison between SVC and STATCOM in Flicker Mitigation of Electric Arc Furnace using Practical Recorded Data. International Journal of Smart Electrical Engineering, 03(04), 209-214.en_US
dc.identifier.issn2251-9246
dc.identifier.issn2345-6221
dc.identifier.urihttp://ijsee.iauctb.ac.ir/article_518743.html
dc.identifier.urihttps://iranjournals.nlai.ir/handle/123456789/308652
dc.description.abstractElectric arc furnace (EAF) is one of the largest loads in electric power systems. It is highly time varying and nonlinear. Its reactive power variations cause voltage fluctuations in nearby system which is known as flicker. On the other hand the nonlinear voltage-current characteristic causes strong voltage and current harmonics in EAF. To this end Flexible AC Transmission Systems (FACTS) technologies are used to mitigate the flicker and harmonics caused by EAF. The mostly used FACTS device in EAFs is Static VAr compensator (SVC) which can reduce the flicker and harmonics to some levels. Delays relevant to reactive power measurement and thyristor ignition reduce compensation capabilities of SVC. In order to prevent these delays, one can use faster compensation devices. Static Synchronous Compensator (STATCOM) may be considered as a high performance candidate for this purpose due to its fast and flexible response. In this article the performance of STATCOM is compared to SVC in EAFs plants. For this purpose the system is simulated with SVC and STATCOM in PSCAD/EMTDC using the practical EAF data records.  Data records are the instantaneous EAF voltage and current recorded from EAFs in Mobarakeh steel company in Esfahan/Iran.en_US
dc.format.extent463
dc.format.mimetypeapplication/pdf
dc.languageEnglish
dc.language.isoen_US
dc.publisherIslamic Azad University,Central Tehran Branchen_US
dc.relation.ispartofInternational Journal of Smart Electrical Engineeringen_US
dc.subjectElectric Arc Furnaceen_US
dc.subjectEAF, Reactive poweren_US
dc.subjectFlicker, SVC, STATCOMen_US
dc.titleA Comparison between SVC and STATCOM in Flicker Mitigation of Electric Arc Furnace using Practical Recorded Dataen_US
dc.typeTexten_US
dc.typeResearch Paperen_US
dc.contributor.departmentSchool of Electrical and Computer Engineering,Shiraz University,Shiraz, Iran.en_US
dc.contributor.departmentSchool of Electrical and Computer Engineering,Shiraz University,Shiraz, Iran.en_US
dc.citation.volume03
dc.citation.issue04
dc.citation.spage209
dc.citation.epage214