    Assessment of Extremely Low Frequency (ELF) Electric and Magnetic Fields in Hamedan High Electrical Power Stations and their Effects on Workers

    (ندگان)پدیدآور
    Ghorbani Shahna, FarshidEshaghi, MahboobehDehghanpour, TaherehKarami, Zohre
    Thumbnail
    دریافت مدرک مشاهده
    FullText
    اندازه فایل: 
    583.0کیلوبایت
    نوع فايل (MIME): 
    PDF
    نوع مدرک
    Text
    Original Paper
    زبان مدرک
    English
    نمایش کامل رکورد
    چکیده
    Introduction: Public and occupational exposure to extremely low frequency (ELF) electric and magnetic fields induced by electrical equipment is a significant issue in the environment and at the workplace due to their potential health effects on public health. The purpose of this study was assessment of the electric and magnetic fields intensities and determination of mental and psychological effects of occupational exposure in the high voltage electric power stations in the city of Hamadan, Iran. Material and Methods: The intensities of the magnetic and electric fields were measured at eight high voltage electric power stations at three different intervals of sources using an HI-3604 instrument. A two-part questionnaire was used to assess mental and psychological effects of the exposure to these fields. Two groups of control and case workers including 30 samples were selected to determine the exposure effects. Results: The results of field measurements showed the highest average electric field intensity was related to the CVT unit with 3110 V/m at a 2 m distance from the source and the lowest average was related to the control room with 1.35 V/m next to the source. Also, the highest and lowest magnetic field intensities were close to the transformator 2 and the battery room (50.42 and 1.31 mG), respectively. Discussion and Conclusion: The intensities of electric and magnetic fields in the selected stations are lower than the ACGIH and ICNIRP standard levels for occupational exposures. The results obtained indicate that the distribution of these fields was nonlinear around the sources and the effects observed on exposed workers were non-thermal.
    کلید واژگان
    electric field
    Extremely Low Frequency
    Magnetic Field
    Mental Effects
    Psychological Effects
    Bioelectricity & Biomagnetic
    Medical Physics

    شماره نشریه
    3
    تاریخ نشر
    2011-09-01
    1390-06-10
    ناشر
    Mashhad University of Medical Sciences
    سازمان پدید آورنده
    Assistant Professor, Occupational Health Dept., Faculty of Public Health and Research Center for Health Science, Hamedan University of Medical Sciences, Hamedan, Iran.
    Ph.D. Student of Occupational Health, Faculty of Public Health, Hamedan University of Medical Sciences, Shiraz, Iran.
    B.Sc. of Occupational Health, Faculty of Public Health, Hamedan University of Medical Sciences, Shiraz, Iran.
    B.Sc. of Occupational Health, Faculty of Public Health, Hamedan University of Medical Sciences, Shiraz, Iran.

    شاپا
    2345-3672
    URI
    https://dx.doi.org/10.22038/ijmp.2011.7230
    http://ijmp.mums.ac.ir/article_7230.html
    https://iranjournals.nlai.ir/handle/123456789/324162

    مرور

    همه جای سامانهپایگاه‌ها و مجموعه‌ها بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌هااین مجموعه بر اساس تاریخ انتشارپدیدآورانعناوینموضوع‌‌ها

    حساب من

    ورود به سامانهثبت نام

    آمار

    مشاهده آمار استفاده

    تازه ترین ها

    تازه ترین مدارک
    © کليه حقوق اين سامانه برای سازمان اسناد و کتابخانه ملی ایران محفوظ است
    تماس با ما | ارسال بازخورد
    قدرت یافته توسطسیناوب